| Generator Set |
| Model Number | 5402 |
| Rated Power (LP / NG) | 30/29 |
| Rated Amps @ 60 Hz 240 V, 1Ø | 125/120.8 |
| Surge Watts - 240V, 1 Ø | 48960 |
| Surge Amps | 204 |
| Engine | 1.6L/4 Cyl. |
| Alternator RPM | 3600 |
| Enclosure | Steel |
| Whisper Test | Yes |
| Sound Level (dBA @ exercise) | 62 |
| (dBA @ normal operation) | 75 |
| Dimensions (L" x W" x H") | 62x29x34 |
| Compatible Transfer Switches | RTS |
| Unit Weight (lbs.) | 935 |
| Transfer Switches |
| No. of Poles | 2 |
| Current Rating (amps) | 200 |
| Voltage Rating (VAC) | 250 |
| Utility Voltage Monitor (fixed) | |
| - Pick-up | 0.8 |
| - Drop out | 0.6 |
| Return to Utility | Approx. 15 seconds |
| Exercises 15 minutes weekly | Standard |
| UL 1008 Listed | Yes |
| Dimensions | See Specification Sheet |
| Enclosure Type | NEMA 3R (Outdoor rated) |
| Weight (lbs.) | 35 |
| GenReady |
| GenReady Load Center with EZ Transfer Operator | |
| Only applicable for generators that are 30 kW and smaller | |
| Main Breaker Amperage | 200 |
| Voltage | 120/240, 1ø |
| Generator Protected Circuits – Feeder Breaker Amperage | 125 |
| Utility Sensing Circuit Breaker | 1x15 Amp 1 pole |
| Maximum Number of Protected Circuits | 18 (30 with tandem breakers) |
| Maximum Number of Non-protected Circuits | 10 |
| Enclosure Type | NEMA 1 |
| Service Entrance Rated | Yes |
| External Dimensions (H" x W" x D") | 42 x 14.5 x 4 |
| Controls |
| Engine Start Sequence | Cyclic cranking: 7 sec. on, 7 sec. rest. 90 sec. maximum duration |
| Automatic Low Oil Shutdown | Standard |
| Overspeed Shutdown | Standard, 72 Hz |
| Overcrank Protection | Standard |
| Automatic Voltage Regulator with Over-Voltage Protection | Standard |
| Engine Warmup | 10 seconds |
| Engine Cool-Down | 1 minute |
| Safety Fuse | Standard |
| Starter Lockout | Starter cannot re-engage until 5 seconds after the engine has stopped |
| 2.5 Amp Timed Trickle Battery Charger | Standard |
| WhisperTest: Sound Output dB(A) at 23 ft. with generator in exercise mode | 63 |
| Auto Switch | Automatic start on utility failure/7 day exercise |
| Off Switch | Stops unit. Power is removed. Control and charger still operate |
| Manual / Test (start) | Start with starter control, unit stays on. If utility fails, transfer to load takes place |
| Full Monitoring System | Oil pressure, coolant temperature, engine speed, coolant level, cranking time, starter lockout, utility sensing |
| Shutdown and LED Indicators | Overspeed and overcrank, low oil pressure, high collant temperature, low coolant level, low fuel pressure, low battery voltage |